11/12/2023 0 Comments Dometic brisk 2 ac![]() Make sure DC volts are within operation range and 115 volts are supplied to the AC power module board.įor rooftop air conditioners, follow these instructions to troubleshoot: Verify configuration operation before troubleshooting the AC power module. The board is a signal receiver and completes AC volt circuits according to what signal it receives. The 3-amp fuse is the only replaceable component. Replace power module board on units that are not equipped with a replaceable control box. If any of these are defective, the complete control box must be replaced. The AC power module consists of relays, dip switches, plug receptacles, and other components. If the previous checks are not correct, the relay is defective and should be replaced.If the above checks are correct, the relay is good.There should be continuity between terminals COM and NO. Energize the coil with DC volts (10 to 16).There should be no continuity between terminals COM to NO. Next, verify the relay coil is not energized (no DC power). ![]()